Dust emission monitoring
AirSafe Continuous Dust Monitoring in Ambient Air
A standalone instrument that monitors dust concentration in ambient air, in control system areas, silo areas, boiler houses and work stations. It alarms against a limit you set, so dust escaping from a process is caught early.

- Helps prevent dust explosion zones from forming
- Dust concentrations at work stations are safely monitored
- Dust escaping from system parts is detected quickly
- Early detection for dust that could endanger the workplace
- Also suited to zone 22 dust applications
Use
Where AirSafe fits
AirSafe is a standalone instrument for measuring dust concentration in ambient air, in places such as control rooms, silo areas, boiler houses and work stations. It is built on triboelectric sensor technology proven in thousands of process-system applications.
It monitors against preset limit values. That helps keep dust from building up into a dust explosion hazard, catches dust escaping unnoticed from a process, and gives early warning of dust that could endanger people.
Function and system
How AirSafe measures dust in the air
AirSafe consists of a flow duct with an integrated triboelectric dust sensor. It draws air through the duct at about 100 m³/h (59 cfm). Dust carried in the air stream passes the sensor and produces a charge transfer, which is used as the measurement signal.
The flow duct is 500 mm (19.7 in) long with a 100 × 100 mm (3.9 × 3.9 in) square cross-section. The sensor has a relay output that switches when the set limit is exceeded.
The unit is supplied pre-calibrated, with the alert point at about 25 mg/m³. You can adjust the threshold from about 5 to 150 mg/m³ in 5 mg steps by pressing a button.
Outputs
- Contact closure (relay)
- RS 485 link to a wall-mount or DIN rail transmitter, which provides a 4–20 mA signal and Modbus RTU for PC connection
Visualization software displays and saves up to 10 measuring points and can export the data to other programs such as Excel.



Mounting and installation
Mount it anywhere in the room
AirSafe can be installed anywhere in a room. No clearance from equipment or walls is needed, except where ambient temperatures are high. It mounts on a wall with the brackets included.
Technical data
AirSafe specifications
Imperial values are converted from the manufacturer's metric data. Confirm critical values against the product information PDF.
| Measured objects | Solid particles in a gas stream |
|---|---|
| Particle size | 0.3 µm and larger |
| Measurement range | From 0.1 mg/m³ |
| Ambient temperature | −20 to +60 °C (−4 to +140 °F) |
| Humidity | Up to 95% RH, non-condensing |
| Measurement principle | Triboelectric |
| Damping time | 1 s |
| Output signals | Relay, normally closed or normally open |
| Dimensions | 500 × 100 × 240 mm L × W × H (19.7 × 3.9 × 9.4 in) |
| Housing material | Aluminium |
| Protection rating | IP65 |
| Power supply | 24 V DC ±10% |
| Power rating | Max. 10 W |
| Electrical connection | Screw terminals |
| Weight | 5.5 kg (12.1 lb) |
| Power supply | 24 V DC ±10% |
|---|---|
| Power consumption | 20 W / 24 VA |
| Protection type | IP 40 to EN 60529 |
| Ambient operating temperature | −10 to +45 °C (+14 to +113 °F) |
| Dimensions | 23 × 90 × 118 mm W × H × D (0.9 × 3.5 × 4.6 in) |
| Weight | Approx. 172 g (6.1 oz) |
| Terminal conductor cross-section | 0.2–2.5 mm² (AWG 24–14) |
| Current output | 4–20 mA (or 0–20 mA), load under 500 Ω |
| Alarm switch output | Changeover relay, max. 250 V AC, 1 A |
| Interface | Modbus over RS 485 |
| Data backup | Flash memory |
Application examples
AirSafe in real processes



Common questions
AirSafe FAQ
What does AirSafe monitor?
The dust concentration in ambient air, in places such as control rooms, silo areas, boiler houses and work stations.
How does AirSafe work?
It draws air through a flow duct at about 100 m³/h. Dust in the air stream passes an integrated triboelectric sensor and produces a charge transfer, which is the measurement signal.
What alarm level does AirSafe use?
It is supplied pre-calibrated with the alert point at about 25 mg/m³. The threshold is adjustable from about 5 to 150 mg/m³ in 5 mg steps.
What outputs does AirSafe provide?
A relay contact, and an RS 485 link to a wall-mount or DIN rail transmitter that provides a 4–20 mA signal and Modbus RTU.
Where can AirSafe be installed?
Anywhere in a room, on a wall with the included brackets. No clearance from equipment or walls is needed, except where ambient temperatures are high.
Can AirSafe be used in dust Ex zones?
It is also suited to zone 22 dust applications.
Talk with GTS
Is AirSafe right for your facility?
Tell us what dust you handle and which rooms you need to monitor. We'll confirm whether AirSafe fits or recommend a better option.