Moisture measurement
M-Sens 2 Online Moisture Measurement
A sensor for continuous moisture measurement in dry bulk solids. It records both surface and capillary moisture, works independently of the material flow, and fits container outlets, conveyor belts, screws, mixers and dryers.

- Moisture range of 0 to 65%, depending on the material
- Measurement accuracy of 0.1%
- Online moisture measurement
- Independent of the material flow
- Temperature-resistant up to 120 °C (248 °F)
- ATEX-certified
- Records both surface moisture and capillary moisture
Use
Where M-Sens 2 fits
M-Sens 2 measures moisture continuously in solids of all kinds. Suggested installations are container outlets, conveyor belts, conveyor screws, mixers and conveyor dryers.
It is a contact method, so the ceramic measuring disc has to stay covered with material.
The sensor is ATEX-certified, with optional Ex protection for zone 20 (dust) and zone 0 (gas).





Function
How the measurement works
M-Sens 2 uses high-frequency measurement with direct digitalization, which gives high resolution.
Surface and capillary moisture strongly affect a material's dielectric constant, so moisture can be determined precisely when the bulk density is constant. An internal filter offsets fluctuations caused by bulk density, and temperature-related fluctuations are compensated automatically.
Calibration is done on site by pressing a button and entering a moisture reference value.

Mounting and installation
Mounting positions
The measuring field penetrates even dense materials such as sand. The minimum material depth is 120 mm (4.7 in), and the probe should face the material to avoid reflection problems.
- Container: a standard connection flange is available.
- Conveyor belt: a material skimmer creates a constant material height for online measurement.
- Conveyor screw: mount in the lower third of the screw, where the volume of material passing the sensor stays nearly constant.
- Free-fall or inclined pipe: a catching mechanism holds material in front of the probe for the measurement, then a flap reopens so the material drops on. Measurements can repeat at short or long intervals.




Technical data
M-Sens 2 specifications
Converted values are added in brackets. Confirm critical values against the product information PDF.
| Housing | Stainless steel 1.4571 |
|---|---|
| Sensor surface | Ceramic |
| Protection category | IP 67 according to EN 60529 |
| Ex protection (optional) | Zone 20 (dust), zone 0 (gas) |
| Material ambient temperature | 0 to +120 °C (+32 to +248 °F) |
| Working pressure | Max. 10 bar (145 psi) |
| Power consumption | 0.6 W |
| Weight | Approx. 1.0 kg (2.2 lb) |
| Response time | 0.1 seconds |
| Measuring range | 0 to 65% residual moisture, depending on the material |
| Accuracy | 0.1% absolute in the calibrated measuring range |
| Connecting cable | Shielded, 4-wire, 0.25 mm² |
| Power supply | 110/230 V AC (50 Hz) or 24 V DC |
|---|---|
| Power consumption | 20 W / 24 V |
| Current consumption | Max. 1 A at 24 V |
| Protection category | IP 65 according to EN 60529 |
| Operating temperature | −10 to +45 °C (+14 to +113 °F) |
| Dimensions | 258 × 237 × 174 mm W × H × D (10.2 × 9.3 × 6.9 in) |
| Weight | Approx. 2.5 kg (5.5 lb) |
| Interface | RS 232, RS 485 |
| Cable glands | 3 × M16 (4.5–10 mm Ø) |
| Cable cross-section | 0.2–2.5 mm² (AWG 24–14) |
| Current output signal | 1 × 4–20 mA (0–20 mA), load < 500 Ω |
| Switched output, measuring alarm | Relay, two-way contact, max. 250 V AC, 1 A |
| Digital inputs | 2 inputs for active external control signals |
| Data protection | Flash |
Application examples
M-Sens 2 moisture measurement in real processes









Common questions
M-Sens 2 FAQ
What does M-Sens 2 measure?
Moisture in dry bulk solids, continuously, from 0 to 65% residual moisture depending on the material.
How accurate is M-Sens 2?
0.1% absolute in the calibrated measuring range.
How does M-Sens 2 work?
It uses high-frequency measurement with direct digitalization. Surface and capillary moisture affect the material's dielectric constant, which the sensor reads. An internal filter offsets bulk density fluctuations.
Where can M-Sens 2 be installed?
On container outlets, conveyor belts, conveyor screws, mixers, conveyor dryers and free-fall or inclined pipes. The ceramic measuring disc has to stay covered with material, to a depth of at least 120 mm (4.7 in).
How is M-Sens 2 calibrated?
On site, by pressing a button and entering a moisture reference value.
What temperature and pressure can M-Sens 2 handle?
Material temperatures from 0 to 120 °C (32 to 248 °F) and a working pressure up to 10 bar (145 psi).
Talk with GTS
Is M-Sens 2 right for your material?
Tell us what material you're measuring, where it moves and the moisture range you expect. We'll confirm whether M-Sens 2 fits or recommend a better option.